Maximum wire length calculator

Rearranging the voltage drop formula gives the longest run that stays within a limit: maximum length = drop limit × voltage × 1000 ÷ (2 × current × resistance per 1000 ft), with 1.732 instead of 2 for three-phase. A 12 AWG copper circuit at 120 volts and 20 amps reaches about 45 feet at 3%. VoltageDrop shows the maximum length for the wire you pick below the result.

Copper or aluminum, AWG / kcmil

    Saved you some time? Leave a tip, entirely optional.

    Lighter loads go further: the same wire at 10 amps reaches about 91 feet, because the drop is proportional to the current.

    How the voltage drop calculator works

    VoltageDrop uses VD = 2 × I × R × L ÷ 1000 for DC and single-phase circuits and VD = 1.732 × I × R × L ÷ 1000 for three-phase, where I is the current in amps, R the conductor resistance in ohms per 1000 ft and L the one-way length in feet. Percent drop = VD ÷ supply voltage × 100. The suggested wire is the smallest size whose drop is within your limit and whose ampacity covers the current (125% of it for a continuous load).

    Wire gauge chart

    Sizemm²Copper Ω/1000 ftAluminum Ω/1000 ftCopper amps (75 °C)Aluminum amps (75 °C)
    18 AWG0.8237.95———
    16 AWG1.314.99———
    14 AWG2.083.14—20 (15 A breaker)—
    12 AWG3.311.983.2525 (20 A breaker)20 (15 A breaker)
    10 AWG5.2611.242.0435 (30 A breaker)30 (25 A breaker)
    8 AWG8.3670.7781.285040
    6 AWG13.30.4910.8086550
    4 AWG21.150.3080.5088565
    3 AWG26.670.2450.40310075
    2 AWG33.620.1940.31911590
    1 AWG42.410.1540.253130100
    1/0 AWG53.490.1220.201150120
    2/0 AWG67.430.09670.159175135
    3/0 AWG85.010.07660.126200155
    4/0 AWG107.20.06080.1230180
    250 kcmil1270.05150.0847255205
    300 kcmil1520.04290.0707285230
    350 kcmil1770.03670.0605310250
    400 kcmil2030.03210.0529335270
    500 kcmil2530.02580.0424380310

    Resistance: NEC Chapter 9 Table 8, stranded uncoated copper and aluminum, DC at 75 °C. Ampacity: NEC Table 310.16, 75 °C column (not more than three current-carrying conductors, 30 °C ambient); breaker limits for 14–10 AWG from NEC 240.4(D). 18 and 16 AWG are shown for low-voltage DC only.

    Limits of this calculator

    Results are estimates for planning. The calculation uses DC resistance and ignores reactance and power factor, conductor temperature below 75 °C, and derating for heat, conduit fill or bundling. Terminal temperature ratings, insulation type, local codes and the equipment instructions can all require a larger wire. Have a licensed electrician design and inspect mains-voltage work.

    Frequently asked questions

    How far can you run 12 gauge wire on a 20 amp circuit?

    About 45 ft at the full 20 A to stay within 3% at 120 V, or about 76 ft at 5%. Many circuits never carry the full rating.

    How far can you run 14 gauge wire on 15 amps?

    About 38 ft at full load for 3% at 120 V.

    How far can you run 10 gauge wire at 30 amps?

    About 97 ft at 240 V for a 3% drop, or 48 ft at 120 V.